  1. BEFORE INSTALLING TANK: Fill tank with water to insure that tank was not damaged in transit. The tanks are air and water tested before they leave the plant. WARRANTY COVERS PARTS ONLY
  2. DO NOT under any circumstance use the water in this tank as a Potable water supply.
  3. DO NOT expose tank to direct sunlight or artificial ultraviolet light of any kind, (examples: fluorescent, tanning lights, etc.)
  4. DO NOT allow tank to come into direct contact with open flame.
  5. DO NOT expose tank to temperatures greater than 120 degrees F (49 degrees C) or less than 40 degrees F (4 degrees C).
  6. Water in tank MUST NOT BE ALLOWED TO FREEZE, use anti-freeze solution to prevent sprinkler piping from freezing.
  7. Tank must sit on a LEVEL, CLEAN, FLAT SURFACE.
  8. SURFACE SHALL BE STRUCTURALLY SOUND to support weight of tank, Pump, and water.
    300 gal tank approx. 350 lbs. empty, 3000 lbs. filled
    450 gal tank approx. 450 lbs. empty, 4500 lbs. filled
    550 gal tank approx. 380 lbs. empty, 5000 lbs. filled
  9. In areas where AQUATIC GROWTH is present a water conditioner MUST BE used & maintained. Contact local water authority for type of conditioner to use.

FAILURE TO COMPLY WITH ANY OF THE ABOVE MAY AFFECT THE TANKS ABILITY TO HOLD WATER OR WORK PROPERLY.

FROM A RELIABLE WATER SOURCE

  1. TANK FILL LINE
    Connect a 3/4" domestic line with a shut off valve to opening in the top of the tank. If AUTO-FILL VALVE is supplied, install a pressure reducing valve in supply line if pressure exceeds 80 psi. CHECK VALVE OPERATION MONTHLY FOR LEAKAGE
  2. WATER BY PASS LINE
    Connect a 3/4" domestic line with an indicating valve to the BY-PASS 3/4" backflow preventer.
  3. SPRINKLER SUPPLY PIPE
    Connect sprinkler pipe to 11/4" or 11/2" SPRINKLER line.
  4. TANK DRAIN / OVERFLOW
    IMPORTANT !!
    WATER DAMAGE CAN OCCUR IF NOT CONNECTED TO DRAIN
    (Water may seep back through system into tank)
    CONNECT 1" pipe to DRAIN outlet, pipe to a suitable drain.

IT IS OUR RECOMMENDATION THAT A LICENSED ELECTRICIAN MAKE ALL ELECTRICAL CONNECTIONS AS REQUIRED BY LOCAL AUTHORITIES.

Customer to furnish and have installed MAIN CIRCUIT BREAKER PROTECTION.

This circuit shall be dedicated for pump/tank only.

CHECK WITH LOCAL ELECTRICAL CODES FOR PROPER SIZE OF BREAKER AND WIRE.

BASIC / STANDARD CONTROLLERS

For 110 Volt 1 Phase Installation

  1. Connect power lead to MOTOR STARTER TERMINAL 'L1' IN CONTROL BOX
  2. Connect neutral to MOTOR STARTER TERMINAL 'L2' IN CONTROL BOX
  3. Connect ground to ground lug

For 230 Volt 1 Phase Installation **3 Wires Required Plus Ground Wire**

  1. Connect power lead to MOTOR STARTER TERMINAL 'L1' IN CONTROL BOX
  2. Connect power lead to MOTOR STARTER TERMINAL 'L2' IN CONTROL BOX
  3. Connect neutral to TERMINAL STRIP 'N' IN CONTROL BOX
  4. Connect ground to ground lug

DO NOT CONNECT POWER TO PRESSURE SWITCH

13R CONTROLLER

Single Pump Installation - 230 Volt 1 Phase Installation

  1. Connect power lead to MOTOR STARTER TERMINAL L1A
  2. Connect power lead to MOTOR STARTER TERMINAL L2A
  3. Connect neutral to CONNECTOR 'N' on terminal strip
  4. Connect ground to ground lug

Dual Pump Installation - 230 Volt 1 Phase Installation

  1. Connect power lead to MOTOR STARTER TERMINAL L1A
  2. Connect power lead to MOTOR STARTER TERMINAL L2A
  3. Connect neutral to CONNECTOR 'N' on terminal strip
  4. Connect ground to ground lug

PUMP ELECTRICAL DATA GUIDELINES
*Check local electrical codes for proper size of breaker protection

   

FULL LOAD AMPS

HP

RPM

115V/230

1

3500

14.0/7.0

1.5

3500

20.0/10.0

2

3500

21/10.5

3

3500

NA/10.0

5

3500

NA/23.0

BASIC CONTROLLER

  1. Alarm devices are not included.
  2. Connect wiring from alarm device to flow switch. Remove flow switch cover with special wrench. (supplied)
  3. Flow switch is supplied with 2 sets of dry contacts. (N.O. or N.C.)
  4. Flow switch has a built in adjustable retard device. Factory setting is set between '0' & 'A' 10-15 seconds delay in signal.

STANDARD CONTROLLER
(Has internal testing circuit built in)

  1. Alarm bell (other devices) not included.
  2. Controller is pre-wired for use with 110-volt alarm devices. Connect 110 VOLT ONLY bell (other devices) to terminal strip # 7 & # 2 in control box. Pressing test button on controller cover can test device.
  3. For other voltage devices, a set of dry contacts is located in the flow switch.
    a. Remove flow switch cover with special wrench. (supplied)
    b. Wire to N.O. or N.C. contact to device. NOTE: Test button will not activate this device. Test must be performed through device.
  4. To ring 110-volt bell for valve closing, connect either black wire from valve to terminal #7 in control box.

13R CONTROLLER

Flow Switch

  1. Alarm devices are not included.
  2. Connect wiring from alarm device to flow switch. Remove flow switch cover with special wrench (supplied)
  3. Flow switch is supplied with 2 sets of dry contacts. (N.O or N.C.)
  4. Flow switch has a built in adjustable retard device. Factory setting is set between '0' & 'A' 10-15 seconds delay in signal.

Controller

  1. Contacts are supplied for:
    a. Controller in pump running condition
    b. Loss of line power
  2. See controller data enclosed with controller