1. Determine the demand of the sprinkler system in gallons and psi at the discharge of the pump by the use of hydraulic calculations. (example: 30 gpm @ 40 psi required)

2. Tank size -- multiply the gallons required by the duration in minutes required. (NFPA 13D 10 minutes, NFPA 13R 30 minutes) Tanks may have to be manifolded together to obtain longer duration. (example: 30 gpm x 10 minutes = 300 gallon tank)

3. Pump size -- select pump from psi/gallon chart. (example: 40 psi @ 30 gpm required = 1.5 hp pump)

4. Determine what electrical power is available. 115 or 230 volt single phase motors are in stock.

5. Select type of controller. Basic, Standard or Residential. Click here to learn more about our controllers.

Click here to download a PDF for Pump Curves

Gallons 0 20 30 40 50 60 70 80 90 100
1 HP 49 43 37 31            
1.5 HP 59 51 45 39            
2 HP 68 60 55 49            
3 HP 48 47 46 45 43 42 40 38 35 33
5 HP 59 58 57 57 56 55 53 52 49 47
2-3 HP 96 94 92 90 87 84 80 76 71 66
5 HP SSH 71 69 68 67 65 63 59 55 53 52
7.5 HP SSH 94 91 90 88 85 82 77 73 70 67
10 HP SSH 113 111 108 107 105 103 99 95 90 86
Above numbers are in PSI @ discharge of pump